The EL9410 power supply terminal is used to refresh the E-bus. Data is exchanged between the coupler and the EtherCAT Terminal over the E-bus. Each terminal draws a certain amount of current from the E-bus (see “current consumption E-bus” in the technical data). This current is fed into the E-bus by the relevant coupler’s power supply unit. In configurations with a large number of terminals it is possible to use the EL9410 in order to supply an extra 2 A to the E-bus. The EL9410 has a diagnostic function which is displayed by LED and on the process image.
Technology: power supply terminal
Short-circuit proof: yes
Input voltage: 24 V DC (-15 %/+20 %)
Input current: 70 mA + (E-bus/4)
Output voltage: 5 V for E-bus supply
Output current: 2A
Electrical isolation: 500 V (E-bus/field potential)
Power contacts: max. 24 V DC/max. 10 A
Diagnostics in the process image: yes
Special features: standard EL supply
Weight: approx. 65 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP20/variable
Pluggable wiring: for all ESxxxx terminals
Approvals/markings: CE, UL, ATEX
Ex marking: II 3 G Ex nA IIC T4 Gc
>>> Refer to technical document: el9410
Reviews
There are no reviews yet.