The KL1184 digital input terminal acquires the binary 24\u00a0V\u00a0DC control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains four channels that indicate its signal state by means of light emitting diodes.<\/p>\n
Special features:<\/strong><\/p>\n
<\/p>\n
Product information:<\/strong><\/span><\/p>\n
Technical data<\/th>\n | KL1184<\/th>\n<\/tr>\n<\/thead>\n |
---|---|
Connection technology<\/td>\n | 2-\/3-wire<\/td>\n<\/tr>\n |
Specification<\/td>\n | ground switching<\/td>\n<\/tr>\n |
Number of inputs<\/td>\n | 4<\/td>\n<\/tr>\n |
Nominal voltage<\/td>\n | 24 V DC (-15%\/+20%)<\/td>\n<\/tr>\n |
\u201c0\u201d signal voltage<\/td>\n | 18\u202630 V<\/td>\n<\/tr>\n |
\u201c1\u201d signal voltage<\/td>\n | 0\u20267 V<\/td>\n<\/tr>\n |
Input filter<\/td>\n | typ. 3.0 ms<\/td>\n<\/tr>\n |
Input current<\/td>\n | typ. 5 mA<\/td>\n<\/tr>\n |
Current consumption K-bus<\/td>\n | typ. 8 mA<\/td>\n<\/tr>\n |
Electrical isolation<\/td>\n | 500 V (K-bus\/field potential)<\/td>\n<\/tr>\n |
Bit width in the process image<\/td>\n | 4 inputs<\/td>\n<\/tr>\n |
Configuration<\/td>\n | no address or configuration setting<\/td>\n<\/tr>\n |
Weight<\/td>\n | approx. 55 g<\/td>\n<\/tr>\n |
Operating\/storage temperature<\/td>\n | 0\u2026+55\u00b0C\/-25\u2026+85\u00b0C<\/td>\n<\/tr>\n |
Relative humidity<\/td>\n | 95%, no condensation<\/td>\n<\/tr>\n |
Vibration\/shock resistance<\/td>\n | conforms to EN 60068-2-6\/EN 60068-2-27<\/td>\n<\/tr>\n |
EMC immunity\/emission<\/td>\n | conforms to EN 61000-6-2\/EN 61000-6-4<\/td>\n<\/tr>\n |
Protect. rating\/installation pos.<\/td>\n | IP20\/variable<\/td>\n<\/tr>\n |
Pluggable wiring<\/td>\n | for all KSxxxx Bus Terminals<\/td>\n<\/tr>\n |
Approvals\/markings<\/td>\n | CE, UL, ATEX, IECEx<\/td>\n<\/tr>\n |
Ex marking<\/td>\n | ATEX: \nII 3 G Ex ec IIC T4 Gc \nIECEx: \nEx ec IIC T4 Gc<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n |