{"id":131857,"date":"2024-04-10T14:16:46","date_gmt":"2024-04-10T07:16:46","guid":{"rendered":"https:\/\/sunly.com.vn\/products\/bx9000-bo-dieu-khien-dau-cuoi-bus-ethernet-tcp-ip"},"modified":"2024-04-10T14:21:05","modified_gmt":"2024-04-10T07:21:05","slug":"bx9000-ethernet-tcp-ip-bus-terminal-controller","status":"publish","type":"product","link":"https:\/\/sunly.com.vn\/en\/products\/bx9000-ethernet-tcp-ip-bus-terminal-controller","title":{"rendered":"BX9000 | Ethernet TCP\/IP Bus Terminal Controller"},"content":{"rendered":"

The BX9000 Bus Terminal Controller has an\u00a0Ethernet<\/a><\/span>\u00a0slave\/master interface. The controller has automatic transmission rate detection up to 100\u00a0Mbit. The address can optionally be entered via DHCP, BootP, ARP or with the joystick switch. Up to 2\u00a0kbytes of input and 2\u00a0kbytes of output can be exchanged with the controller. The ModbusTCP and the ADS\/TCP and ADS\/UDP protocols are implemented.<\/p>\n

One unit consists of the BX9000 Bus Terminal Controller with up to 64 Bus Terminals and a bus end terminal. With the terminal bus extension system, the connection of up to 255 Bus Terminals is possible.<\/p>\n

The controller is programmed via the COM1 or via the Ethernet interface. In terms of their equipment and performance, the BX series Bus Terminal Controllers are positioned between the BC series Bus Terminal Controllers and the CX series Embedded PCs. The main features distinguishing BC and BX are the larger memory and the expanded interfaces of the BX. Additionally, two serial interfaces are integrated for programming and for the connection of further serial devices. The device itself comprises an illuminated LC display with two lines of 16 characters each, a joystick switch and a real-time clock. Further peripheral devices, e.g. displays, can be connected via the integrated Beckhoff Smart System Bus (SSB).<\/p>\n

Controller for distributed signal processing<\/strong><\/h3>\n

Like for all other Beckhoff controllers, the\u00a0TwinCAT<\/a><\/span>\u00a0automation software is the basis for parameterization and programming. The BX devices are programmed according to the powerful IEC\u00a061131-3 standard in the programming languages IL, FBD, LD, SFC or ST. Users therefore have the familiar TwinCAT tools available, e.g. the PLC programming interface, the System Manager and TwinCAT Scope. Data is exchanged optionally via the serial port (COM1) or via the Ethernet interface.<\/p>\n

The configuration is also carried out using TwinCAT. The fieldbus interface, the SSB bus and the real-time clock can be configured and parameterized via the System Manager. The System Manager can read all connected devices and Bus Terminals. After the parameterization, the configuration is saved on the BX via the serial interface and can be accessed again later.<\/p>\n

\"BX9000<\/p>\n

Product information:<\/span><\/strong><\/h2>\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n
Technical data<\/th>\nBX9000<\/th>\n<\/tr>\n<\/thead>\n
Number of Bus Terminals<\/td>\n64 (255 with K-bus extension)<\/td>\n<\/tr>\n
Max. number of bytes fieldbus<\/td>\n512 byte input and 512 byte output<\/td>\n<\/tr>\n
Max. number of bytes process image<\/td>\n2048 byte input and 2048 byte output<\/td>\n<\/tr>\n
Digital peripheral signals<\/td>\n2,040 inputs\/outputs<\/td>\n<\/tr>\n
Analog peripheral signals<\/td>\n512 inputs\/outputs<\/td>\n<\/tr>\n
Protocol<\/td>\nTwinCAT ADS, Modbus TCP<\/td>\n<\/tr>\n
Data transfer rates<\/td>\n10\/100 Mbit\/s, automatic recognition of the transmission rate<\/td>\n<\/tr>\n
Bus interface<\/td>\nRJ45<\/td>\n<\/tr>\n
Serial interface<\/td>\nCOM1: 1 x RS232, COM2: 1 x RS232 or RS485<\/td>\n<\/tr>\n
SSB<\/td>\nCANopen-based subsidiary bus system for the connection of further peripheral devices<\/td>\n<\/tr>\n
Diagnostics LED<\/td>\n2 x power supply, 2 x K-bus<\/td>\n<\/tr>\n
Display<\/td>\nFSTN display with 2 x 16 characters for diagnosis or own texts, illuminated<\/td>\n<\/tr>\n
Switch<\/td>\njoystick switch for parameterisation and diagnosis<\/td>\n<\/tr>\n
Clock<\/td>\nbattery-powered real-time clock for time and date<\/td>\n<\/tr>\n
Power supply<\/td>\n24 V DC (-15%\/+20%)<\/td>\n<\/tr>\n
Input current<\/td>\n140 mA + (total K-bus current)\/4, 500 mA max.<\/td>\n<\/tr>\n
Starting current<\/td>\n2.5 x continuous current<\/td>\n<\/tr>\n
Current supply K-bus<\/td>\n1450 mA<\/td>\n<\/tr>\n
Power contacts<\/td>\nmax. 24 V DC\/max. 10 A<\/td>\n<\/tr>\n
Electrical isolation<\/td>\n500 V (power contact\/supply voltage)<\/td>\n<\/tr>\n
Weight<\/td>\napprox. 250 g<\/td>\n<\/tr>\n
Operating\/storage temperature<\/td>\n0\u2026+55\u00b0C\/-25\u2026+85\u00b0C<\/td>\n<\/tr>\n
Relative humidity<\/td>\n95%, no condensation<\/td>\n<\/tr>\n
Vibration\/shock resistance<\/td>\nconforms to EN 60068-2-6\/EN 60068-2-27<\/td>\n<\/tr>\n
EMC immunity\/emission<\/td>\nconforms to EN 61000-6-2\/EN 61000-6-4<\/td>\n<\/tr>\n
Protect. rating\/installation pos.<\/td>\nIP20\/variable<\/td>\n<\/tr>\n
Approvals\/markings<\/td>\nCE, UL<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n

>>> REFER TO TECHNICAL DOCUMENT:\u00a0BX9000en<\/a>\n","protected":false},"excerpt":{"rendered":"

BRAND: BECKHOFF\u00a0\u00a0<\/span><\/p>\n

PRODUCT CODE: BX9000<\/span><\/p>\n

CATEGORY: BUS TERMINALS<\/span><\/p>\n

SUPPLIER: SUNLY<\/span><\/p>\n","protected":false},"featured_media":131840,"comment_status":"open","ping_status":"closed","template":"","meta":[],"_links":{"self":[{"href":"https:\/\/sunly.com.vn\/en\/wp-json\/wp\/v2\/product\/131857"}],"collection":[{"href":"https:\/\/sunly.com.vn\/en\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/sunly.com.vn\/en\/wp-json\/wp\/v2\/types\/product"}],"replies":[{"embeddable":true,"href":"https:\/\/sunly.com.vn\/en\/wp-json\/wp\/v2\/comments?post=131857"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/sunly.com.vn\/en\/wp-json\/wp\/v2\/media\/131840"}],"wp:attachment":[{"href":"https:\/\/sunly.com.vn\/en\/wp-json\/wp\/v2\/media?parent=131857"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}