KL3054 | Bus Terminal, 4-channel analog input, current, 4…20 mA, 12 bit, single-ended
The job of the KL3054 analog input terminal is to transmit analog measurement signals with electrical isolation to the automation device. The input electronics is independent of the supply voltage of the power contacts. The ground connection is the reference potential for the inputs. The error LEDs indicate an overload condition and a broken wire. The KL3054 combines four channels in one housing.
Number of inputs 4
Signal current 4…20 mA
Technology single-ended
Internal resistance 80 Ω + diode voltage 0.7 V
Common-mode voltage UCM –
Conversion time ~ 4 ms
Resolution 12 bit
Measurement error/ uncertainty < ±0.3 % (relative to full scale value)
Surge voltage resistance max. 35 V
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 75 mA
Bit width in the process image input: 4 x 16 bit data (4 x 8 bit control/status optional)
Configuration no address or configuration setting
Special features for 2-wire sensors
Weight approx. 70 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx, DNV GL, cFMus
Pluggable wiring for all KSxxxx Bus Terminals
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc
>>> Refer to technical document: kl304x_kl305xen