The EL2535-xxxx output terminals control the output current through pulse width control of the supply voltage. They are electrically isolated from the E-bus. The current values (0 to maximum output current) are specified by the automation device through a 16-bit value. The output stages are protected against overload and short circuit. Each EtherCAT Terminal contains two channels whose signal state is indicated by LEDs. The light emitting diodes simplify local diagnosis by displaying typical load and wiring faults.
Special features:
- 2 PWM outputs with push-pull output stage
- Suitable for inductive loads > 1 mH
- ±2 A max. output current per channel at 24 V DC rated voltage
Connection technology: PWM output, push-pull outputs
Number of outputs: 2
Nominal voltage: 24 V DC (-15 %/+20 %)
Nominal voltage: 24 V DC (-15 %/+20 %)
Load type: inductive > 1 mH
Max. output current: ±2 A
Short-circuit current: typ. < 4 A
PWM clock frequency: 30 kHz default
Duty factor: 0…100 % (current-controlled)
Resolution: 10 bit
Reverse voltage protection: yes
Current consumption E-bus: typ. 110 mA
Electrical isolation: 500 V (E-bus/field potential)
Current consumption power contacts: typ. 30 mA + load
Bit width in the process image: 48 inputs/outputs: 2 x 16 bit data, 2 x 8 bit control/status
Special features: 2 digital 24 V inputs
Weight: approx. 50 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.: IP20/see documentation
Pluggable wiring: for all ESxxxx terminals
Approvals/markings: CE, UL, ATEX, IECEx, cFMus
Ex marking: ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc
>>> Refer to technical document: EL2535en