The KL1012 digital input terminal acquires the binary 24 V DC control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains two channels that indicate their signal state by means of LEDs.
Special features:
- input specification type 1/3
- low delay due to 0.2 ms input
Technical data KL1012 Connection technology 4-wire Specification EN 61131-2, type 1 Number of inputs 2 Nominal voltage 24 V DC (-15%/+20%) “0” signal voltage -3…+5 V “1” signal voltage 15…30 V Input filter typ. 0.2 ms Input current typ. 5 mA Current consumption K-bus typ. 3 mA Electrical isolation 500 V (K-bus/field potential) Bit width in the process image 2 inputs Configuration no address or configuration setting Weight approx. 50 g Operating/storage temperature -25…+60°C/-40…+85°C Relative humidity 95%, no condensation Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27 EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4 Protect. rating/installation pos. IP20/variable Pluggable wiring for all KSxxxx Bus Terminals Approvals/markings CE, UL, ATEX, IECEx, DNV GL Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
>>> REFER TO TECHNICAL DOCUMENT: kl1xxxen