The KL1212 digital input terminal acquires the binary 24 V DC control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains two channels whose signal states or errors are indicated by LEDs. The KL1212 generates a short-circuit proof 24 V DC supply voltage for sensors. A short circuit or a wire breakage in the sensor supply is detected, and the terminal status is relayed to the controller via the K-bus.
Special features:
- input specification type 1
- no bouncing due to mechanical switches thanks to 3 ms input filter
- short-circuit proof sensor supply
- possibility to diagnose open circuit and short circuit
Product information:
Technical data | KL1212 |
---|---|
Connection technology | 3-wire |
Specification | EN 61131-2, type 1 |
Number of inputs | 2 |
Nominal voltage | 24 V DC (-15%/+20%) |
“0” signal voltage | -3…+5 V |
“1” signal voltage | 15…30 V |
Input filter | typ. 3.0 ms |
Input current | typ. 5 mA |
Sensor supply max. | 0.5 A (short-circuit-proof) |
Current consumption K-bus | typ. 8 mA |
Electrical isolation | 500 V (K-bus/field potential) |
Bit width in the process image | input/output: 4 inputs (2 error bits/2 signal bits); 2 outputs (2 sensor supply) |
Input/output bit assignments | input: bit 3 bit 2 bit 1 bit 0 output: bit 1 bit 0 err. 2 err. 1 on 2 on 1 off 2 off 1 |
Configuration | no address or configuration setting |
Weight | approx. 55 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals/markings | CE, UL, ATEX, IECEx, DNV GL |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Reviews
There are no reviews yet.