The KL1314 digital input terminal acquires the binary 24 V DC control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal has four channels, whose signal state is displayed by light emitting diodes.
Special features:
- input specification type 2
- low delay due to 0.2 ms input filter
Product information:
Technical data | KL1314 |
---|---|
Connection technology | 2-/3-wire |
Specification | EN 61131-2, type 2 |
Number of inputs | 4 |
Nominal voltage | 24 V DC (-15%/+20%) |
“0” signal voltage | -3…+5 V (EN 61131-2, type 2) |
“1” signal voltage | 11…30 V (EN 61131-2, type 2) |
Input filter | typ. 0.2 ms |
Input current | typ. 6 mA (EN 61131-2, type 2) |
Current consumption K-bus | typ. 3 mA |
Electrical isolation | 500 V (K-bus/field potential) |
Bit width in the process image | 4 inputs |
Configuration | no address or configuration setting |
Weight | approx. 50 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals/markings | CE, UL, ATEX, IECEx |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Reviews