KL3062 | Bus Terminal, 2-channel analog input, voltage, 0…10 V, 12 bit, single-ended
The KL3062 analog input terminal handles signals in the range from 0 to 10 V. The voltage is digitized to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the Bus Terminal have a common ground potential, the reference ground. The run LEDs give an indication of the data exchange with the Bus Coupler.
Number of inputs 2
Power supply via the K-bus
Signal voltage 0…10 V
Technology single-ended
Internal resistance typ. > 200 kΩ
Common-mode voltage UCM –
Conversion time ~ 2 ms
Resolution 12 bit
Measurement error/ uncertainty < ±0.3 % (relative to full scale value)
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 60 mA
Bit width in the process image input: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration no address or configuration setting
Weight approx. 60 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx
Pluggable wiring for all KSxxxx Bus Terminals
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
>>> Refer to technical document: KL306xen
Reviews