The digital KL1362 input terminal analyzes the input signals of break-in sensors with the aid of a current loop. It enables safe monitoring of alarm contacts with fixed resistance ratio. In addition to the display of the switching state from the sensor, short circuit or open circuit is also detected. The LEDs display the signal states or any error states.
Special features:
- direct connection of break-in sensors
- possibility to diagnose open circuit and short circuit
Product information:
Technical data | KL1362 |
---|---|
Connection technology | 2-wire |
Specification | break-in alarm |
Number of inputs | 2 |
Nominal voltage | 24 V (-15%/+20%) |
“0” signal current | ≤ 1 mA |
“1” signal current | ≥ 1 mA |
Operating voltage | 5.1 V |
Line interruption | < 0.1 mA |
Short-circuit | > 3 mA |
Cable resistance | ≤ 200 Ω |
Input filter | 3.0 ms |
Current consumption K-bus | typ. 35 mA |
Electrical isolation | 500 V (K-bus/field potential) |
Bit width in the process image | 4 inputs |
Configuration | no address or configuration setting |
Special features | monitoring of alarm contacts |
Weight | approx. 55 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals/markings | CE, UL, ATEX, IECEx, DNV GL |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |