The various implementation levels of the TC-Plug differ in the number of thermocouple input channels (12 channels or 32) and in the type of thermocouple implemented (J or K type).
Technical data (Version 1F.1 26.05.2000) FM3332
Dimensions: 120mm x 52mm x 129mm, ,length x wide x height
Connector Hood: Han24B (Harting)
Connector to Thermocouples: Han64D
Contacts: Hard gold plated
Coding system: With coding pins in the connector
Power supply and PROFIBUS connection: Round-Connector, DIN 45322 (series 423, 723 Binder) Shield of the Round-Connector is connected to the plug
Technical data (Version 1F.1 26.05.2000) FM3332
General technical data
Number of thermocouple input channels : 32
Sensor types: type J
Power supply: 24 VDC, -15% …+20% (20.4…28.8 V)
typical operating current: 100 mA (24 V)
max. operating current: 130 mA (24 V)
Power supply input protection
Reverse voltage min. -35V
Over voltage max. 35V
Potential separation
Thermocouples / PROFIBUS: 500 Vrms
Thermocouples / Supply Voltage: 500 Vrms
Supply Voltage / PROFIBUS: 100 Vrms
Ambient temperature
Operating temperature: 0…+55°C
Storage temperature: -25…+85°C
Type of protection plug: IP65 (PROFIBUS-Connector: IP67)
Vibration: EN 60068-2-6 10 Hz <= f <= 57 Hz: 0,075mm Amplitude 57 Hz <= f <= 150 Hz: 1,0 g
Shock: EN 60068-2-27/29 15 g, 11 ms
Vibration: conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
EMC immunity / EMC emission: conforms to EN 61000-6-2 / EN 61000-6-4
Approvals: CE, cULus* *) For the compliance of the cULus requirements use 4 Amp. fuse or class 2 power supply!
Reviews
There are no reviews yet.