The KL1712 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The direct connection of 120 V DC signals for DC and AC voltage is possible. The Bus Terminal contains two channels that indicate its signal state by means of light emitting diodes.
Special features:
- direct connection of 120 V DC signals
- for DC and AC voltage
In addition to the KL1712, there is the KL1712-0010 version with a 24 V AC/DC input circuit.
Product information:
| Technical data | KL1722 |
| Connection technology | 4-wire |
| Number of inputs | 2 |
| Nominal voltage | 120 V AC/DC |
| “0” signal voltage | 0…40 V |
| “1” signal voltage | 80…140 V |
| Input filter | typ. 10 ms |
| Input current | > 3 mA, typ. 6 mA |
| Current consumption K-bus | typ. 3 mA |
| Switching times | 10 ms |
| Electrical isolation | 500 V (K-bus/mains voltage); 3750 V AC, 1 min. |
| Bit width in the process image | 2 inputs |
| Configuration | no address or configuration setting |
| Special features | 120 V AC power grids |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |