The KL1712 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The direct connection of 120 V DC signals for DC and AC voltage is possible. The Bus Terminal contains two channels that indicate its signal state by means of light emitting diodes.
Special features:
- direct connection of 120 V DC signals
- for DC and AC voltage
In addition to the KL1712, there is the KL1712-0010 version with a 24 V AC/DC input circuit.
Product information:
Technical data | KL1722 |
Connection technology | 4-wire |
Number of inputs | 2 |
Nominal voltage | 120 V AC/DC |
“0” signal voltage | 0…40 V |
“1” signal voltage | 80…140 V |
Input filter | typ. 10 ms |
Input current | > 3 mA, typ. 6 mA |
Current consumption K-bus | typ. 3 mA |
Switching times | 10 ms |
Electrical isolation | 500 V (K-bus/mains voltage); 3750 V AC, 1 min. |
Bit width in the process image | 2 inputs |
Configuration | no address or configuration setting |
Special features | 120 V AC power grids |
Weight | approx. 60 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals/markings | CE, UL, ATEX, IECEx |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |