The KL2502 output terminal modulates the pulse width of a binary 24 V DC signal and outputs it electrically isolated from the K-bus. The mark/space ratio is prescribed by a 16 bit value from the automation device. The output stage is protected against overload and short-circuit. The Bus Terminal has two channels, whose signal state is displayed by light emitting diodes. The LEDs are driven in time with the outputs, and show the duty factor by their brightness.
In addition to the KL2502 there is a 5 V DC variant (KL2502-3020) with a PWM clock frequency of up to 30 kHz.
Number of outputs 2
Nominal voltage 24 V DC (-15 %/+20 %)
Load type ohmic
Max. output current 0.1 A (1 A driver component) per channel
PWM clock frequency 1 Hz…20 kHz, 250 Hz default
Duty factor 0…100 % (TON > 750 ns, TOFF > 500 ns)
Resolution max. 10 bit
Electrical isolation 500 V (K-bus/field potential)
Current consumption power contacts typ. 10 mA + load
Current consumption K-bus typ. 18 mA
Bit width in the process image 48 inputs/outputs: 2 x 16 bit data, 2 x 8 bit control/status
Configuration no address setting, configuration via Bus Coupler or controller
Weight approx. 50 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals/markings CE, UL, ATEX, IECEx, cFMus
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc