KL3403 | Bus Terminal, 3-channel analog input, power measurement, 500 V AC, 1 A, 16 bit
The KL3403 Bus Terminal enables the measurement of all relevant electrical data of the supply network. The voltage is measured via the direct connection of L1, L2, L3 and N. The current of the three phases L1, L2 and L3 is fed via simple current transformers. All measured currents and voltages are available as root-mean-square values. In the KL3403 version, the effective power and the energy consumption for each phase are calculated. Through the relationship of the root-mean-square values of voltage U * current I and the effective power P, all other information such as the apparent power S or the phase shift angle cos φ can be derived. For each fieldbus, KL3403 provides a comprehensive network analysis and an energy management option.
The KL3403 Bus Terminal can be ordered to suit further current and voltage ranges, such as 5 A, 20 mA or 333 mV. An overview of the different versions can be found under ordering information.
Number of inputs 3 x current, 3 x voltage
Technology 3-phase power measurement
Measured values current, voltage, effective power, energy, cos φ, peak values U, I and P, frequency
Measuring voltage max. 500 V AC 3~ (ULX-N: max. 288 V AC)
Measuring current max. 1 A, via measuring transformers x A/1 A
Resolution 16 bit (21 bit, internal)
Measurement error/ uncertainty 0.5 % relative to full scale value (U, I), 1 % calculated value
Measuring procedure true RMS with 64,000 samples/s
Update time 50 ms per measured value preset, free configurable
Electrical isolation 1500 V (K-bus/field potential)
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 115 mA
Bit width in the process image input/output: 3 x 16 bit data, 3 x 8 bit control/status
Special features energy meter, power measurement, true RMS
Weight approx. 75 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL
Pluggable wiring for all KSxxxx Bus Terminals
>>> Refer to: KL340x_KL346xen
Reviews