KL9110 | Potential supply terminal, 24 V DC, with diagnostics
The KL9110 power feed terminal makes it possible to set up various potential groups with the standard voltage of 24 V DC. In order to monitor the supply voltage, the terminal with diagnostics reports the status of the power feed terminal to the Bus Coupler through two input bits. It is thus possible for the controller to check the distributed peripheral voltage over the fieldbus.
Current load ≤ 10 A
Integrated fine-wire fuse –
Power LED green
Defect LED –
Diagnostics yes
Current consumption K-bus typ. 10 mA
Nominal voltage 24 V DC
Electrical isolation yes
Reported to K-bus yes
PE contact yes
Shield connection –
Renewed infeed yes
Connection facility to additional power contact 1
K-bus, looped through yes
Bit width in the process image 1
Electrical connection to DIN rail –
Housing width 12 mm
Weight approx. 50 g
Side by side mounting on Bus Terminals with power contact yes
Side by side mounting on Bus Terminals without power contact yes
Operating/storage temperature -25…+60 °C/-40…+85 °C
Pluggable wiring for all KSxxxx Bus Terminals
Approvals/markings CE, UL, ATEX, IECEx, DNV GL, cFMus
Ex marking ATEX:
II 3 G Ex nA IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc
>>> Refer to technical document: kl91xx_kl92xxen