The KL2404 digital output terminal connects the binary 24 V control signals electrically isolated with the actuators. The Bus Terminal contains four channels that indicate their signal state by means of LEDs. The 4-channel Bus Terminal enables the direct connection of four 2-wire sensors. Four ground connection points are provided.
Connection technology 2-wire
Number of outputs 4
Nominal voltage 24 V DC (-15 %/+20 %)
Load type ohmic, inductive, lamp load
Max. output current 0.5 A (short-circuit proof) per channel
Short-circuit current < 2 A
Breaking energy < 150 mJ/channel
Reverse voltage protection yes
Electrical isolation 500 V (K-bus/field potential)
Current consumption power contacts typ. 30 mA + load
Current consumption K-bus typ. 9 mA
Bit width in the process image 4 outputs
Configuration no address or configuration setting
Weight approx. 70 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals/markings CE, UL, ATEX, IECEx
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc