The KL2612 output terminal switches two relays, each having one changeover contact, under control of the automation device. It has potential-free contacts. The power contacts are not looped through.
Number of outputs 2 x change-over
Nominal voltage 125 V AC/30 V DC
Load type ohmic
Max. output current 2 A per channel
Switching current 0.5 A AC/2 A DC (ohmic)
Ohmic switching current 0.5 A AC/2 A DC
Inductive switching current no data
Minimum permitted load 10 µA at 10 mV
Lamp test, electronic ballast max. 2 A starting current
Electrical isolation 500 V (K-bus/field potential)
Current consumption power contacts –
Current consumption K-bus typ. 60 mA
Bit width in the process image 2 outputs
Operating cycles mech. (min.) 1 x 108
Operating cycles electr. (min.) 2 x 105 (1 A/30 V DC)
Configuration no address or configuration setting
Special features signal relay
Weight approx. 80 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals/markings CE, UL, DNV GL
Ex marking II 3 G Ex nA IIC T4 Gc
>>> Refer to technical document: kl26xxen
Reviews