KL3454 | Bus Terminal, 4-channel analog input, current, 4…20 mA, 12 bit, single-ended
The KL3454 analog input terminal processes signals in the range between 4 and 20 mA. The current is digitized to a resolution of 12 bits and is transmitted, in an electrically isolated form, to the higher-level automation device. In the KL3454, the four inputs are 2-wire versions and have a common ground potential. The 24 V power contact is connected to the terminal, in order to enable the connection of 2-wire sensors without external supply. The power contacts are connected through. The reference ground for all inputs is the 0 V power contact. Overload is detected. The terminal status is relayed to the controller via the K-bus. The run LEDs indicate the data exchange with the Bus Coupler, the error LEDs overload or wire breakage.
Number of inputs 4
Power supply via the K-bus
Signal current 4…20 mA
Technology single-ended
Internal resistance < 85 Ω
Common-mode voltage UCM –
Conversion time ~ 2 ms
Resolution 12 bit
Measurement error/ uncertainty < ±0.3 % (relative to full scale value)
Surge voltage resistance 30 V DC
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts load only
Current consumption K-bus typ. 85 mA
Bit width in the process image input: 4 x 16 bit data (4 x 8 bit control/status optional)
Configuration no address or configuration setting
Special features –
Weight approx. 55 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx, DNV GL
Pluggable wiring for all KSxxxx Bus Terminals
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
>>> Refer to technical document: KL344x_KL345xen
Reviews
There are no reviews yet.