The KL3061 analog input terminal handles signals in the range from 0 to 10 V. The voltage is digitized to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the Bus Terminal have a common ground potential, the reference ground. The KL3061 is characterized by its fine granularity and electrical isolation. The run LEDs give an indication of the data exchange with the Bus Coupler.
Number of inputs 1
Power supply via the K-bus
Signal voltage 0…10 V
Technology single-ended
Internal resistance typ. > 200 kΩ
Common-mode voltage UCM –
Conversion time ~ 1 ms
Resolution 12 bit
Measurement error/ uncertainty < ±0.3 % (relative to full scale value)
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 60 mA
Bit width in the process image input: 1 x 16 bit data (1 x 8 bit control/status optional)
Configuration no address or configuration setting
Weight approx. 60 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx
Pluggable wiring for all KSxxxx Bus Terminals
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc