KL3312 | Bus Terminal, 2-channel analog input, temperature, thermocouple, 16 bit
The KL3312 analog input terminal allows thermocouples to be connected directly. The Bus Terminal’s circuitry can operate thermocouple sensors using the 2-wire technique. Linearization over the full temperature range is realized with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminals. The KL3312 can also be used for mV measurement
Number of inputs 2
Power supply via the K-bus
Technology 2-wire
Thermocouple sensor types types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Connection method 2-wire
Measuring range in the range defined in each case for the sensor (default setting: type K; -100…+1370 °C);
mV measurement: ±30 mV…±120 mV
Conversion time ~ 250 ms
Wiring fail indication yes
Resolution 0.1 °C per digit
Measurement error/ uncertainty < ±0.5 % (relative to full scale value)
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 65 mA
Bit width in the process image input: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration no address setting, configuration via Bus Coupler or controller
Weight approx. 70 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
>>> Refer to technical document: kl331x_kl3302en